                  科普安防知識

                  廣告位招租

                  弱電安防工程的驗收規范(一)

                    關于弱電工程驗收規范的事情,大家可以參照規范,也可以自己公司整理一套驗收規范,對于一般的工程還是比較適用的,本文可以作為參考。

                  弱電安防工程的驗收規范

                    一、總則

                    1.為統一弱電安防工程施工質量檢查,隨工檢驗和竣工驗收本工作參照國家相關標準,制定本規范。

                    2.本規范適用于新建、擴建、改建弱電安防工程的驗收。

                    3.本規范為弱電安防工程能用驗收規范,考慮到各弱電安防工程的系統配置不盡相同,驗收項目可適當增減,以設計方案描述的功能為準。

                    4.本規范尚在不斷充實完善,本規范中未涉及系統的驗收主要驗收施工質量及系統功能,并以設計方案描述的功能為準。

                    二、綜合布線系統驗收規范

                    1. 一般規定

                    (1)系統的工程驗收應由工程的施工單位、建設單位代表組成驗收小組,按設計方案的要求進行。驗收時應做好記錄,簽署驗收證書,并應立卷,歸檔。

                    (2)各工程項目驗收合格后,方可交付使用。當驗收不合格時,施工單位返修直到合格后,再行驗收。

                   ?、傧到y的驗收應包括下列內容:

                   ?、谙到y工程的施工質量;

                   ?、巯到y質量的測試;

                   ?、?圖紙、資料的移交。

                    2. 系統的工程施工質量

                    (1)系統的工程施工質量應按施工要求進行驗收,檢查的項目和內容應符合下表的規定。

                  項目

                  內容

                  抽查百分數(%)

                  交接間、

                  設備間、

                  設備機柜、

                  機架

                  1、規格、外觀

                  2、安裝垂直、水平度;

                  3、各種螺絲必須緊固;

                  4、油漆不得脫落,標志完整齊全。

                  100

                  面板安裝

                  1、面板允許水平誤差<2mm;

                  2、面板允許垂直誤差<2mm;

                  3、面板距地面300mm。

                  5

                    (2)建設單位應對隱蔽工程工程隨工驗收、凡經過檢驗合格的辦理簽證,在進行竣工驗收時,可不再進行檢驗。

                    3. 系統質量測試

                    (1)系統的測試應符合下列規定:

                  項目

                  內容

                  抽查百分比(%)

                  基本鏈路

                  電氣測試

                  1、接線圖測試。

                  2、測試長度。

                  3、基本鏈路衰減,信道減測試。

                  4、近揣串音測試。

                  5

                  通斷測試

                  線路是否為通路。

                  100

                    表1 信道衰減量

                  頻率(MHZ)

                  3類(dB)

                  5類(dB)

                  1.00

                  4.2

                  2.5

                  4.00

                  7.3

                  4.5

                  8.00

                  10.2

                  6.3

                  10.00

                  11.5

                  7.0

                  16.00

                  14.9

                  9.2

                  20.00

                  ____

                  10.3

                  25.00

                  ____

                  11.4

                  31.25

                  ____

                  12.8

                  62.50

                  ____

                  18.5

                  100.00

                  ____

                  24.0

                    表2 基本鏈路衰減量

                  頻率(MHZ)

                  3類(dB)

                  5類(dB)

                  1.00

                  4.2

                  2.5

                  4.00

                  7.3

                  4.5

                  8.00

                  10.2

                  6.3

                  10.00

                  11.5

                  7.0

                  16.00

                  14.9

                  9.2

                  20.00

                  ____

                  10.3

                  25.00

                  ____

                  11.4

                  31.25

                  ____

                  12.8

                  62.50

                  ____

                  18.5

                  100.00

                  ____

                  24.0

                    在選定的某一頻率上信和到和基本鏈路衰減量應符合上表的要求,信道的衰減包括10m(跳線、設備連接之和)。

                    表3 信道近端串音(最差線間)

                  頻率(MHZ)

                  3類(dB)

                  5類(dB)

                  1.00

                  39.1

                  60.0

                  4.00

                  29.3

                  50.6

                  8.00

                  24.3

                  45.6

                  10.00

                  22.7

                  44.0

                  16.00

                  19.3

                  40.6

                  20.00

                  ____

                  39.0

                  25.00

                  ____

                  37.4

                  31.25

                  ____

                  35.7

                  62.50

                  ____

                  30.6

                  100.00

                  ____

                  27.1

                    表4 基本鏈路近端串音(最差線間)

                  頻率(MHZ)

                  3類(dB)

                  5類(dB)

                  1.00

                  40.1

                  60.0

                  4.00

                  30.7

                  51.8

                  8.00

                  25.9

                  47.1

                  10.00

                  24.3

                  45.5

                  16.00

                  21.0

                  42.3

                  20.00

                  ____

                  40.7

                  25.00

                  ____

                  39.1

                  31.25

                  ____

                  37.6

                  62.50

                  ____

                  32.7

                  100.00

                  ____

                  29.3

                    近端串音是對電纜內,二條線對間信號的感應。對近端串音的測試,必須對每對線在兩端進行測量。某和頻率上,線對間近端串音應符合上表的要求。

                    4.光纖鏈路測試

                    (1)測試前應對所有的光連接器進行清洗,并將測試接收器校準至零位。

                    (2)測試包括以下內容:

                   ?、賹φ麄€光纖鏈路(包括光纖和連接器)的衰減進行測試;

                   ?、诠饫w鏈路的反射測量以確定鏈路長度及故障點位置。

                   ?、酃饫|布線鏈路在規定的傳輸窗口測量出的最大光衰減應不超過下表的規定。

                    光纜布線鏈路的衰減

                  布 線

                  鏈路長度

                  (m)

                  衰 減(db)

                  單模光纖

                  多模光纖

                  1310nm

                  1550 nm

                  850 nm

                  1300 nm

                  水 平

                  100

                  2.2 nm

                  2.5 nm

                  2.2 nm

                  2.7 nm

                  建筑物主干

                  500

                  2.7 nm

                  2.7 nm

                  3.5 nm

                  2.6 nm

                  建筑群主干

                  1500

                  3.6 nm

                  3.6 nm

                  7.4 nm

                  m

                    (3)光纖布線鏈路的任一接口測出的光回波損耗應大于下表給出的值。

                    最小光波損耗

                  類 別

                  單 模 光 纖

                  多 模 光 纖

                  波長

                  1310nm

                  1550nm

                  850nm

                  1300nm

                  光波損耗

                  26 db

                  26db

                  20db

                  b

                    5. 竣工驗收

                    在系統的工程竣工驗收前,施工單位按下列內容編制竣工驗收文件一式三份交建設單位,其中一份由建設單位簽收蓋章后,退還給施工單位存檔。

                    (1)系統圖;

                    (2) 設備概要說明書;

                    (3) 設備器材一覽表;

                    (4) 工程質量驗收記錄;

                    (5)工程驗收記錄;

                    (未完待續)

                  打賞

                  取消

                  感謝您的支持,我會繼續努力的!

                  掃碼支持
                  掃碼打賞,你說多少就多少

                  打開支付寶掃一掃,即可進行掃碼打賞哦

                  弱電   監控系統
                  分享到:

                  廣告位招租

                  您可以還會對下面的安防文章感興趣:

                1. 家庭常用電纜線徑對應功率與負荷
                2. 安防術語:1080P、4K、8K的含義和區別
                3. 弱電工程項目都有哪些崗位?各崗位職責是什么?
                4. 智能化弱電工程橋架、支吊架、線管、線盒安裝要求
                5. 中控信息:1.25億元中標貴州省智慧監獄建設項目
                6. 最新安防評論

                  留言與評論(共有 0 條評論)
                  驗證碼:
                  国产精品免费_区二区三区观看

                    <address id="vtd1x"></address>

                      <sub id="vtd1x"></sub>

                              <address id="vtd1x"><delect id="vtd1x"><output id="vtd1x"></output></delect></address>

                              <address id="vtd1x"><dfn id="vtd1x"></dfn></address>

                                <sub id="vtd1x"><dfn id="vtd1x"></dfn></sub><sub id="vtd1x"><delect id="vtd1x"><output id="vtd1x"></output></delect></sub>
                                <address id="vtd1x"></address>

                                <font id="vtd1x"><delect id="vtd1x"></delect></font>
                                <form id="vtd1x"><var id="vtd1x"><ins id="vtd1x"></ins></var></form>
                                <sub id="vtd1x"></sub>

                                <address id="vtd1x"><dfn id="vtd1x"></dfn></address>

                                  <address id="vtd1x"></address>

                                <sub id="vtd1x"><var id="vtd1x"><ins id="vtd1x"></ins></var></sub>

                                <address id="vtd1x"></address>
                                <address id="vtd1x"><dfn id="vtd1x"></dfn></address>

                                <address id="vtd1x"></address>